| Signal delay | |
| Rated operating current | 40 mA (without sensors) / max. 240 mA |
| Auxiliary voltage (output) | 20 … 30 V DC PELV |
| Supply | from AS-Interface |
| AS-Interface specification | V3.0 |
| Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
| Altitude | 2000 m above MSL |
| Slave type | Standard slave |
| Voltage | 12 … 31 V |
| Protection class | III |
| ID code | F |
| ID1 code | F |
| Current | 2 A per output TB 40 ?°C: 6 A total TB 70 ?‚?°C: sum O1 + O2 max. 2 A, sum O3 + O4 max. 2 A |
| Input current | 9 mA (limited internally) |
| Degree of protection | EN 60529:2000 |
| Voltage | (UAUX — 0.5 V) |
| Degree of protection | IP68 / IP69K |
| Ambient temperature | -25 … 70 ?°C (-13 … 158 ?°F) |
| Connection | AS-Interface/UAUX: AS-Interface flat cable or M12 round connector Inputs/outputs: M12 round connector |
| Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC |
| Pollution degree | 3 |
| Required master specification | V2.1 |
| LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply i.e. overload or lead interruption outputs |
| ID2 code | E |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
| Fieldbus standard | EN 62026-2:2013 |
| IO code | 7 |
| Rated operating voltage | 18,0 … 31.6 V from AS-Interface |
| Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
| Shock and impact resistance | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
| Input/Output | safe isolation, rated insulation voltage 40 V DC |
| AS-Interface | EN 62026-2:2013 |
| Input | EN 61131-2:2007 |
| Profile | S-7.F |
| Mass | 200 g |
| Current loading capacity | 200 mA, overload and short-circuit protected |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| Storage temperature | -25 … 85 ?°C (-13 … 185 ?°F) |
| Climatic conditions | For indoor use only |
| Tightening torque, cable gland | 0.4 Nm |
| Parameter bits (programmable via AS-i) | function |
| Vibration resistance | 0.75 mm 10 … 57 Hz , 5 g 57 … 150 Hz, 20 cycles |
| LED IN | switching state (input); 4 LED yellow |
| Output/AS-Interface | safe isolation, rated insulation voltage 40 V DC |
| UL File Number | E223772 |
| Mounting | Mounting plate |
| Data bits (function via AS-Interface) | inputoutput |
| Relative humidity | 85 % , noncondensing |
| Switching point | according to DIN EN 61131-2 (Type 2) |
| Emitted interference | EN 61000-6-4:2007 |
| LED OUT | switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption |
| Tightening torque, housing screws | 1.8 Nm |
| Supply | from external auxiliary voltage UAUX |
Buy Pepperl+Fuchs VAA-4E4A-G11-ZAJ/EA2L-FV1 with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. is an online electrical distributor. We offer a wide range of electronic automation products. We ship to any location in the world. We provide discounts of 5% or more to regular customers. We’ve made it easy for you to find spare parts. We understand your needs and constantly strive to work more efficiently to solve them.