| UL File Number | E223772 |
| Fieldbus standard | EN 62026-2:2013 |
| IO code | 7 |
| Temperature influence | Voltage/current: 20 ppm/K Pt100: (10 ppm of indicated temperature [?°C] + 0.003 ?°C)/K |
| Parameter bits (programmable via AS-i) | function |
| ID2 code | D |
| Rated operating voltage | 26.5 … 31.6 V from AS-Interface |
| LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
| Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. |
| Mounting | Mounting plate |
| Emitted interference | EN 61000-6-4:2007 |
| Climatic conditions | For indoor use only |
| Mission Time (TM) | 20 a |
| Ambient temperature | -25 … 70 ?°C (-13 … 158 ?°F) |
| Required master specification | V2.1 |
| AS-Interface | EN 62026-2:2013 |
| Rated operating current | 60 mA (without sensors) / max. 200 mA |
| Protection class | III |
| Tightening torque, cable gland | 0.4 Nm |
| LED ANALOG | status of input signal; LED yellow off: not active on: signal within measurement range flashing: signal outside of measurement range |
| Current loading capacity | 140 mA from AS-Interface; overload and short-circuit resistant 600 mA from external auxiliary voltage UAUX , overload and short-circuit protected |
| Measuring current | for Pt100: approx. 1 mA |
| ID1 code | F |
| LED INT/EXT | status display input supply; LED green green: input supply from AS-Interface off: input supply from auxiliary voltage |
| Relative humidity | 85 % , noncondensing |
| ID code | 3 |
| MTTFd | 190 a |
| Mass | 200 g |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
| Auxiliary voltage (output) | 20 … 30 V DC PELV |
| Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| Input resistance | current input: max. 70 andOmega; voltage input: 100 kandOmega; |
| Profile | S-7.3.D |
| AS-Interface specification | V3.0 |
| Supply | from AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT) |
| Storage temperature | -25 … 85 ?°C (-13 … 185 ?°F) |
| Accuracy | Voltage/current: 0.1% of accumulated value Pt100: 0.1% of indicated temperature [?°C] + 0.3 ?°C |
| Resolution | 16 Bit / 1 andmicro;A (current input) or 16 bit / 1 mV (voltage input) or 16 Bit / 0.1?°C (temperature input) |
| Degree of protection | EN 60529:2000 |
| Pollution degree | 3 |
| Input | EN 61131-2:2007 |
| Degree of protection | IP68 / IP69K |
| Diagnostic Coverage (DC) | 0 % |
| Tightening torque, housing screws | 1.8 Nm |
| Number/Type | 2 analog inputs Current: 0 … 20 mA/4 … 20 mA voltage: 0 … 10 V Pt100: -200 … 850 ?°C |
| Connection | AS-Interface/UAUX: cable piercing method, flat cable yellow/flat cable black Inputs: M12 round connector |
| Altitude | 2000 m above MSL |
| Slave type | Standard slave |
Buy Pepperl+Fuchs VBA-2E-G11-I/U/PT100-F with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com is an electrical supply store online. We provide an enhanced product catalog for our clients. Rush shipping is available to any country. We supply only certified products from European brands. We always strive to correspond with the delivery times. Our company has a very well-established supply chain so we always provide the equipment on time and without delay.