| Rated operating current | 35 mA (without sensors) / max. 190 mA |
| Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
| Current | 2 A Per output, total 4 A (TB 60 ?°C) 1 A Per output, total 4 A (TB 70 ?°C) |
| LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
| Required master specification | V3.0 |
| Electrical safety | IEC 61140:2009 |
| Relative humidity | 85 % , noncondensing |
| Input current | 5.6 mA (max.) |
| Functional safety | EN ISO 13849-1:2008 EN ISO 13849-2:2012 |
| Slave type | A/B slave |
| UL File Number | E223772 |
| ID2 code | 7 |
| Supply | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) |
| Degree of protection | EN 60529:2000 |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| Vibration resistance | 0.35 mm 10 … 57 Hz , 5 g 57 … 150 Hz, 20 cycles |
| Current loading capacity | 150 mA, overload- and short-circuit protected (INT) |
| Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
| LED OUT | switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption |
| LED IN | switching state (input); 4 LED yellow |
| Profile | S-7.A.7 |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
| Input | EN 61131-2:2004 |
| LED INT | Internal input supply active; LED green |
| Emitted interference | EN 61000-6-4:2007 |
| MTBF | 141 a |
| LED FAULT | Error display; red LED red: communication error, i.e. address is 0 red flashing: overload internal input supply, i.e. overload or lead interruption outputs |
| Storage temperature | -25 … 85 ?°C (-13 … 185 ?°F) |
| Protection class | III |
| Signal delay | |
| Fieldbus standard | EN 62026-2:2013 |
| Rated operating voltage | 26.5 … 31.6 V from AS-Interface |
| Parameter bits (programmable via AS-i) | function |
| AS-Interface specification | V3.0 |
| Pulse withstand voltage | 0.8 kV |
| Switching point | according to DIN EN 61131-2 (type 1) |
| Number/Type | 4 inputs for 3-wire sensors (PNP), DC |
| AS-Interface | EN 62026-2:2013 |
| ID code | A |
| Surge protection | UEXT, UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) Overvoltage category of the power supplies (primary): III |
| Ambient temperature | -25 … 70 ?°C (-13 … 158 ?°F) |
| Rated insulation voltage | 92 V |
| Mass | 110 g |
| Climatic conditions | For indoor use only |
| Auxiliary voltage (output) | 20 … 30 V DC PELV |
| Altitude | 2000 m above MSL |
| Auxiliary voltage (input) | 12 … 30 V DC PELV |
| Data bits (function via AS-Interface) | inputoutput |
| Usage category | DC-13 |
| Connection | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 … 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 … 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 … 1.5 mm2 |
| Voltage | (UAUX — 0.5 V) |
| Supply | from external auxiliary voltage UAUX |
| IO code | 7 |
| Pollution degree | 2 |
| ID1 code | 7 |
| Voltage | 21 … 31 V DC (INT) |
| Degree of protection | IP20 For safety applications: Installation in an enclosure with a minimum protection class of IP54 required |
| Mounting | DIN mounting rail |