| IO code | 7 |
| Data bits (function via AS-Interface) | inputoutput |
| Mass | 80 g |
| Switching point | according to DIN EN 61131-2 (Type 2) |
| ID1 code | 7 |
| Degree of protection | EN 60529:2000 |
| Usage category | DC-13 |
| Signal frequency | 250 Hz |
| Required master specification | V3.0 |
| Noise immunity | EN 61326-1:2006 |
| ID2 code | 7 |
| Relative humidity | 90 %, noncondensing |
| Rated operating current | 40 mA |
| Protection class | III |
| LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of outputs |
| Storage temperature | -25 … 85 °C (-13 … 185 °F) |
| Number/Type | 4 inputs for 2-wire sensors (PNP), DC or for mechanical contacts |
| Fieldbus standard | EN 62026-2:2013 |
| Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
| Input current | 8 mA (limited internally) |
| Supply | from external auxiliary voltage UAUX |
| Diagnostic Coverage (DC) | 0 % |
| Profile | S-7.A.7 |
| Current | 0.5 A per output , 2 A per module |
| Auxiliary voltage (output) | 20 … 30 V DC PELV |
| Supply | from external auxiliary voltage UAUX |
| Mission Time (TM) | 20 a |
| Parameter bits (programmable via AS-i) | function |
| UL File Number | E87056 |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| Connection | removable spring double terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 … 1.5 mm2 recommended tools for 1.5 mm2: PxC CRIMPFOX ZA3 or Weidmüller PZ 6 roto |
| LED PWR | AS-Interface voltage; LED green |
| Degree of protection | IP20 |
| Input | EN 61131-2:2015 |
| LED OUT | Switching state (output); 4 LED yellow |
| Rated operating voltage | 26.5 … 31.6 V from AS-Interface |
| Voltage | (UAUX — 0.5 V) |
| AS-Interface specification | V3.0 |
| Slave type | A/B slave |
| Signal delay | |
| Pollution degree | 2 |
| MTTFd | 90 a |
| AS-Interface | EN 62026-2:2013 |
| Ambient temperature | -25 … 60 °C (-13 … 140 °F) |
| Emitted interference | EN 55011:2009 |
| ID code | A |
| Mounting | DIN mounting rail |
| Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
| LED IN | switching state (input); 4 LED yellow |
The device features 4 inputs for 2-wire sensors (PNP) or mechanical contacts, and 4 electronic outputs (PNP) with overload and short-circuit protection. The inputs have a switching point according to DIN EN 61131-2 (Type 2). The signal frequency is 250 Hz, and the noise immunity is in accordance with EN 61326-1:2006. The relative humidity is 90% non-condensing, and the rated operating current is 40 mA. The device has protection class III and an error display via a red «LED FAULT» which indicates a communication error or an address of 0, or flashes red for output overload.
The storage temperature ranges from -25 to 85 °C (-13 to 185 °F), while the ambient temperature is -25 to 60 °C (-13 to 140 °F). The mass of the device is 80 g. It has a degree of protection of IP20 according to EN 60529:2000 and EN 61131-2:2015. The usage category is DC-13, and the required master specification is V3.0. The device operates as an A/B slave according to the AS-Interface specification V3.0 (EN 62026-2:2013) with an ID code of 7 (ID1 and ID2) and profile S-7.A.7. The pollution degree is 2, and the MTTFd is 90 years.
The supply is from an external auxiliary voltage UAUX. The rated operating voltage from AS-Interface is 26.5 to 31.6 V. The auxiliary voltage for outputs is 20 to 30 V DC PELV, with a voltage of (UAUX — 0.5 V). The input current is 8 mA (internally limited). The current per output is 0.5 A, and per module is 2 A. The device is designed for mounting on a DIN mounting rail. The connection is made via removable spring double terminals, rated for rigid/flexible wires from 0.25 mm2 to 1.5 mm2.
The «LED AUX» is a dual green/red LED indicating external auxiliary voltage UAUX status: green for voltage OK, red for reverse voltage. The «LED PWR» is a green LED indicating AS-Interface voltage. The «LED OUT» consists of 4 yellow LEDs showing the switching state of the outputs. The «LED IN» consists of 4 yellow LEDs showing the switching state of the inputs. The UL File Number is E87056. Surge protection for UAUX and Uin is provided with Over voltage category III and safe isolated power supplies (PELV).