| General specifications | ||
| Switching element function | PNPNO | |
| Rated operating distance | 1.5 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 … 1.22 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.5 | |
| Nominal ratings | ||
| Operating voltage | 10 … 60 V DC | |
| Switching frequency | 0 … 1500 Hz | |
| Hysteresis | typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | less than or equal to 3 V | |
| Operating current | 0 … 200 mA | |
| No-load supply current | less than or equal to 10 mA | |
| Limit data | ||
| Operating pressure | 350 bar (5076.4 psi) | |
| Functional safety related parameters | ||
| MTTFd | 1240 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -35 … 80 °C (-31 … 176 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | Stainless steel 1.4305 / AISI 303 | |
| Sensing face | Epoxy (black) | |
| Housing diameter | 18 mm | |
| Degree of protection | IP67 | |
Nominal ratings include an operating voltage of 10 to 60 V DC and a switching frequency of 0 to 1500 Hz. The hysteresis is typically 5%. The sensor is protected against reverse polarity and has pulsing short-circuit protection. The voltage drop is less than or equal to 3 V, and the operating current is 0 to 200 mA. The no-load supply current does not exceed 10 mA.
Limit data indicates an operating pressure of 350 bar (5076.4 psi). Functional safety parameters are MTTFd of 1240 a, Mission Time (TM) of 20 a, and Diagnostic Coverage (DC) of 0%.
Approvals include UL (cULus Listed, General Purpose) and CSA (cCSAus Listed, General Purpose). It is certified by China Compulsory Certification (CCC). The ambient temperature range is -35 to 80 °C (-31 to 176 °F).
Mechanical specifications include a 2 m PVC cable with a core cross-section of 0.34 mm². The housing material is Stainless steel 1.4305 / AISI 303, and the sensing face is epoxy (black). The housing diameter is 18 mm, and the degree of protection is IP67.