| Connection | backplane bus |
| Electromagnetic compatibility | NE 21:2007 |
| ATEX approval | BVS 11 ATEX E 116X |
| Occupied slots | 1 |
| Relative humidity | 95 % non-condensing |
| Vibration resistance | EN 60068-2-6:2008 |
| Environmental test | EN 60068-2-14:2009 |
| Storage temperature | -25 … 85 °C (-13 … 185 °F) |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) |
| Shock resistance | EN 60068-2-27:2009 |
| Number of channels | 4 |
| Connection | backplane bus |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Conversion time | max. 100 ms |
| Transmitter supply voltage | min. 15 V at 20 mA ; 21.5 V at 4 mA |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** |
| Connection | 2-wire transmitter (HART): supply circuit: channel I 1+, 2-, channel II 3+, 4-, channel III 5+, 6-, channel IV 7+, 8- |
| Resolution | 12 Bit (0 … 26 mA) |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool |
| IECEx approval | BVS 11.0068X |
| UL approval | E106378 |
| Power consumption | 2.7 W |
| System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| EU-Type Examination Certificate | BVS 11 ATEX E 116 X |
| HART communication | yes |
| Relative humidity | EN 60068-2-78:2001 |
| Degree of protection | IEC 60529:2000 |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 … 1.5 mm²) or screw terminals (0.08 … 1.5 mm²) |
| Refresh time | 100 ms |
| Damaging gas | EN 60068-2-42:2003 |
| Mass | approx. 90 g |
| Interface | manufacturer-specific bus to standard com unit |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
| HART secondary variable | no |
| Power dissipation | 1.5 W |
| Degree of protection | IP20 when mounted on backplane |
| Input resistance | 15 Ω |
| LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| Vibration resistance | frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ±0.075 mm/1 g; 10 cycles frequency range 5 … 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ±1 mm/0.7 g; 90 minutes at each resonance |
| Coding | optional mechanical coding via front socket |
This device utilizes a backplane bus connection. It is compliant with electromagnetic compatibility standards, including NE 21:2007. The device has ATEX approval (BVS 11 ATEX E 116X) and IECEx approval (BVS 11.0068X), as well as UL approval (E106378). It occupies 1 slot in the system.
The device operates within a relative humidity range of 95% non-condensing. It meets vibration resistance standards EN 60068-2-6:2008 and EN 60068-2-14:2009 for environmental testing. Storage temperature is between -25 and 85 °C (-13 to 185 °F). Dimensions are 16 x 100 x 102 mm (0.63 x 3.9 x 4 inches).
Shock resistance is compliant with EN 60068-2-27:2009. The device features 4 channels. It is designed for operation in environmental conditions according to ISA-S71.04-1985, severity level G3. Conversion time is a maximum of 100 ms. The transmitter supply voltage is a minimum of 15 V at 20 mA or 21.5 V at 4 mA.
The rated voltage is 12 V DC, specifically for use with LB9*** power supplies. The connection type is a 2-wire transmitter (HART) with a supply circuit consisting of channels I, II, III, and IV. Resolution is 12 Bit (0 to 26 mA). Line fault detection can be enabled or disabled per channel via a configuration tool.
Power consumption is 2.7 W. System information indicates the module must be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas, observing the declaration of conformity. For use in hazardous areas (e.g., Zone 2, Zone 22 or Div. 2), the module requires installation in a suitable enclosure.
The ambient temperature range is -20 to 60 °C (-4 to 140 °F). The EU-Type Examination Certificate is BVS 11 ATEX E 116 X. HART communication is supported. Relative humidity compliance is met per EN 60068-2-78:2001. The degree of protection is IEC 60529:2000.
Connection is via a removable front connector with a screw flange (accessory) or through spring terminals (0.14 to 1.5 mm²) or screw terminals (0.08 to 1.5 mm²). Refresh time is 100 ms. Damaging gas resistance is compliant with EN 60068-2-42:2003. The mass is approximately 90 g.
The interface is a manufacturer-specific bus to a standard communication unit. Shock resistance specifications include shock type I, duration 11 ms, amplitude 15 g, and 18 shocks. HART secondary variable is not supported. Power dissipation is 1.5 W. The degree of protection is IP20 when mounted on a backplane. Input resistance is 15 Ω.
LED indication includes a Power LED (green) for supply, a Diagnostic LED (red for module fault, red flashing for communication error, white for fixed parameter set, white flashing for requesting parameters), and Status LEDs (1-4, red for line fault). Supplementary information requires observance of relevant certificates and instructions. Vibration resistance includes frequency ranges 10-150 Hz and 5-100 Hz with specific transition frequencies, amplitudes/accelerations, and durations. Mechanical coding is optional via the front socket.