IECEx approvalIECEx CES 06.0003
| Core cross-section | 0.25 … 1.5 mm2 (24 … 16 AWG) |
| Connection | XG2: terminals 5, 6 |
| Connection | XG2: terminals 1, 3 (+); 2, 4 (-) |
| Ambient temperature | -20 … 60 ?°C (-4 … 140 ?°F) |
| Reverse polarity protection | yes |
| Ripple | ≤ 10 % |
| Fusing | 4 A , in each case for 16 modules |
| Display elements | LED PWR1 (Termination Board power supply), green LED LED PWR2 (Termination Board power supply), green LED LED FAULT (fault indication), red LED — LED lits: power supply failure — LED flashes: module failure LED Run, green LED — The HIMax I/O module is supplied with power and is connected to the Termination Board (FTA) via a system cable. LED Field, red LED — The HIMax I/O module detects faults in the connection between HIMax I/O module and Termination Board (FTA). |
| Material | housing: polycarbonate, 10 % glass fiber reinforced |
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Electromagnetic compatibility | NE 21:2012 For further information see system description. |
| Storage temperature | -40 … 85 ?°C (-40 … 185 ?°F) |
| Degree of protection | IP20 |
| Output type | volt-free contact |
| EC-Type Examination Certificate | CESI 06 ATEX 022 |
| Contact loading | 30 V DC, 1 A |
| Power dissipation | ≤ 500 mW , without modules |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered |
| Degree of protection | IEC 60529:2001 |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): HIMA system connector, 96-pin power supply connection: pluggable spring terminals, black |
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. |
| Mass | approx. 800 g |
| Dimensions | 266 x 200 x 163 mm (10.5 x 7.9 x 6.42 inch) , height including module assembly |