| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions must be observed where applicable. See www.pepperl-fuchs.com for details. |
| Transmitter supply voltage: minimum 15 V at 20 mA, 21.5 V at 4 mA. | |
| LED indication: — Power LED (P) green: supply. — Diagnostic LED (I) red: module fault; red flashing: communication error; white: fixed parameter set (parameters from com unit are ignored); white flashing: requests parameters from com unit. — Status LED (1) red: line fault (lead breakage or short circuit). — Status LED (2) yellow: Live Zero monitoring. | |
| Input resistance: 15 Ω (terminals 5, 6), 236 Ω (terminals 1, 6) HART. | |
| Power consumption: 1.1 W. | |
| Degree of protection: IEC 60529:2000. | |
| INMETRO Brazil: T??V 14.1596X. | |
| System information: The module requires mounting in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). The corresponding EC-type examination certificate must be observed. | |
| Power dissipation: 0.75 W. | |
| Storage temperature: -25 … 85 °C (-13 … 185 °F). | |
| HART secondary variable: yes. | |
| Electromagnetic compatibility: NE 21:2007. | |
| Connection: — 2-wire transmitter (HART): supply circuit: 2/3+, 4/5-. — 3-wire transmitter (HART): supply circuit: 2/3+, 6-; measuring circuit: 4/5+, 6-. — 4-wire transmitter (separately powered): measuring circuit: 4/5+, 6-. — HART measuring circuit: 1+, 6-. | |
| Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18, according to EN 60068-2-27:2009. | |
| Dimensions: 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch). | |
| EU-Type Examination Certificate: BVS 13 ATEX E 050 X. | |
| Resolution: 12 Bit (0 … 26 mA). | |
| Degree of protection: IP20 (module); a separate housing is required according to the system description. | |
| Number of channels: 1. | |
| Ambient temperature: -20 … 60 °C (-4 … 140 °F). | |
| Damaging gas: EN 60068-2-42:2003. | |
| HART communication: yes. | |
| Occupied slots: 1. | |
| Relative humidity: EN 60068-2-78:2001. | |
| Mass: approx. 350 g. | |
| Vibration resistance: frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ±0.075 mm/1 g; 10 cycles. Frequency range 5 … 100 Hz; transition frequency: 13.2 Hz, amplitude/acceleration ±1 mm/0.7 g; 90 minutes at each resonance. | |
| Coding: optional mechanical coding via front socket. | |
| Line fault detection: can be switched on/off for each channel via configuration tool, configurable via configuration tool. | |
| Refresh time: 100 ms. | |
| Connection: backplane bus. | |
| Environmental test: EN 60068-2-14:2009. | |
| Vibration resistance: EN 60068-2-6:2008. | |
| Relative humidity: 95 % non-condensing. | |
| Interface: manufacturer-specific bus to standard com unit. | |
| Connection: backplane bus. | |
| Connection: removable front connector with screw flange (accessory). Wiring connection via spring terminals (0.14 … 1.5 mm²) or screw terminals (0.08 … 1.5 mm²). | |
| ATEX approval: BVS 13 ATEX E 050 X. | |
| Damaging gas: designed for operation in environmental conditions according to ISA-S71.04-1985, severity level G3. | |
| Rated voltage: 12 V DC, only in connection with the power supplies FB92**. | |
| Shock resistance: EN 60068-2-27:2009. |
Pepperl+Fuchs FB3202B2
Одноканальный вход Ex ia для питания 2- или 3-проводных передатчиков, поддерживает HART-связь и горячую замену.
| Дополнительная информация | Сертификат ЕС об испытаниях типа, Заявление о соответствии, Декларация о соответствии, Сертификат соответствия и инструкции должны соблюдаться, где применимо. Информацию см. на http://www.pepperl-fuchs.com. |
|---|---|
| Transmitter supply voltage | min. 15 V at 20 mA ; 21.5 V at 4 mA |
| LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring |
| Входное сопротивление | 15 Ω (terminals 5, 6) 236 Ω (terminals 1, 6) HART |
| Потребляемая мощность | 1.1 W |
| Степень защиты | 57 x 107 x 132 мм (2.2 x 4.2 x 5.2 дюйма) |
| INMETRO | Brazil: T??V 14.1596X |
| Выход со сторожевым таймером | Pepperl+Fuchs Системы удаленного ввода-вывода |
| Рассеиваемая мощность | 0.75 W |
| Температура хранения | -25 … 85 ?°C (-13 … 185 ?°F) |
| HART secondary variable | да |
| Электромагнитная совместимость | NE 21:2007 |
| Подключение | съемный передний разъем с винтовым фланцем (аксессуар)подключение проводов через пружинные клеммы (0,14 … 1,5 мм2) или винтовые клеммы (0,08 … 1,5 мм2) |
| Ударопрочность | EN 60068-2-27:2009 |
| Размеры | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) |
| Сертификат ЕС об испытании типа | BVS 13 ATEX E 050 X |
| Разрешение | 12 Bit (0 … 26 mA) |
| PTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U | 1 |
| Температура окружающей среды | -20 … 60 ?°C (-4 … 140 ?°F) |
| макс. 90 Ом | специфичная для производителя шина для стандартного коммуникационного блока |
| HART communication | да |
| Разрушающий газ | 1 |
| Относительная влажность | 95 % без конденсации |
| Масса | approx. 350 g |
| Виброустойчивость | EN 60068-2-6:2008 |
| Кодировка | PTB 97 ATEX 1074 U |
| Обнаружение неисправностей линии | can be switched on/off for each channel via configuration tool , configurable via configuration tool |
| Refresh time | 100 мс |
| тип удара I, продолжительность удара 11 мс, амплитуда удара 15 g, количество ударов 18 | EN 60068-2-14:2009 |
| Интерфейс | Сторожевой таймер |
| Информация о системе | BVS 13 ATEX E 050 X |
| Номинальное напряжение | Климатические испытания |
FB3202B2 Pepperl+Fuchs FB3202B2 — товар из ассортимента Laserzz для подбора и поставки под задачи ремонта и комплектации.
Позиция подходит для сценариев замены и закупки под конкретную спецификацию оборудования.
Ключевые параметры: Дополнительная информация: Сертификат ЕС об испытаниях типа, Заявление о соответствии, Декларация о соответствии, Сертификат соответствия и инструкции должны соблюдаться, где применимо. Информацию см. на www.pepperl-fuchs.com.; Transmitter supply voltage: min. 15 V at 20 mA ; 21.5 V at 4 mA; LED indication: Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring; Входное сопротивление: 15 Ω (terminals 5, 6) 236 Ω (terminals 1, 6) HART; Потребляемая мощность: 1.1 W.
Для корректного выбора сверяйте маркировку, параметры и совместимость с вашей схемой/узлом.
Вопросы и ответы
Как проверить совместимость товара?
Сравните артикул, технические параметры и формат исполнения с требованиями вашей модели оборудования.
Можно ли заказать партию?
Да, для партийных закупок доступны отдельные условия, ориентируйтесь на количество и сроки поставки.