NAMUR SERIES — diameters 4 — 5 — 6,5 — 8 mm • ATEX certified II 1GD for zone 0,20 • Cable output • Technical data: • Supply voltage according NAMUR: 7,7 ÷ 9 Vdc • Max ripple: 10% • Consumption at 8,2 V with Rx = 1000 Ω with metal: ≤ 1 mA without metal: ≥ 3 mA • Temperature range: — 20° ÷ + 60°C • Max thermal drift of sensing distance Sr : ± 10% • Repeat accuracy (R): 2% • Degree of protection according EN60529: IP67 • Cable conductor cross section: 0,14 mm2 in diameters 4 and 5 mm 0,35 mm2 in diameter 6,5 • Marking: II 1D Ex iaD 20 T80°C II 1G Ex ia IIC T6 • Certified IMQ 08 ATEX 011 X • Electromagnetic compatibility (EMC) according to EN60947-5-2 • According to: EN60947-5-6/EN60079-0/EN60079-11/EN60079-26 • Shock and vibration resistance according to EN60068-2-27/EN60068-2-6 Safety parameters: • Vi max: 13,5 V • Ii max: 60 mA • Ci max: 100 nF • Li max: 100 μH • Pi max: 200 mW These sensors must be used in conjunction with associated apparatus (See Sect. E) Use in hazardous area according to instruction manuals
Технические характеристики
CharacteristicsTechnologyinductiveShapecylindricalOutput signalNAMURMountingthreadedProtection levelexplosion-proof, IP67Measuring range
0.8 mm, 1.5 mm, 2.5 mm (0.03 in)