4 analog input channels RTD sensors, resistance 6500 Ω and 20000 Ω, 2-, 3- or 4-wire Low excitation current 7.5 µA effective, to minimize sensor self-heating errors Individual linearization of the sensor characteristics Sensor specific linearization by using 32 nodes and archive in a sensor data file. Import of manufacturers calibration data High-accuracy digitalization 24-bit ADC, 10 Hz sample rate per channel Signal conditioning linearization, filtering, average, scaling, min/max storage, RMS, arithmetic, alarm 3-Way galvanic isolation 500 VDC channel to channel, channel to power supply, and channel to bus
Технические характеристики
CharacteristicsSignal typeanalogNumber of inputs/outputs4 analog inputs